HS115-3, 4, 5 SERIES CONNECTED TO ANY 115V BURNER MOTOR OR GAS VALVE
(BURNER MOTOR OR GAS VALVE LESS THAN 3 AMPS @ 120 VAC)
MAC-4 CONTROL WIRED WITH UP TO FOUR 24V GAS APPLIANCES AND ONE TJERNLUND
HS115-3,4,5 POWER VENTER (MOTOR LOAD UP TO 1 H.P.)
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM
WARNING:
The BLACK & WHITE Power Venter motor wires shown the diagram below are applicable only for the HS115-3. For models
HS115-4 & HS115-5 use BLACK and WHITE wires from electrical box wip and connect to proper terminals on motor. See motor
nameplate for proper wiring. Upon first startup, as viewed from opposite end of shaft, verify HS115-4 & HS115-5 motors
rotate clockwise. Mount electrical box with Fan Prover in a vertical position. See instructions for proper installation of Fan
Prover Sensing tube. HS115-3,4,5 Motor and Fan Prover specifications are the same as the equivalent HS-3,4,5 model.
Vista de pagina 0
1 2 3 4 5 6 ... 13 14

Indice de contenidos

Pagina 1 - TJERNLUND PRODUCTS, INC

HS115-3, 4, 5 SERIES CONNECTED TO ANY 115V BURNER MOTOR OR GAS VALVE(BURNER MOTOR OR GAS VALVE LESS THAN 3 AMPS @ 120 VAC)MAC-4 CONTROL WIRED WITH UP

Pagina 2

MODELS HS-3, HS-4, HS-5 CONNECTION DIAGRAMS WITH SINGLE APPLIANCEThe diagrams below represent common ways in which the HS-3, HS-4, HS-5 Power Venters

Pagina 3

8MODELS HS-3, HS-4, HS-5 CONNECTED WITH UP TO 3 24V GAS APPLIANCES WITH MAC-3 PART # 950-0460 NOTE:The MAC-3 Multiple Appliance Controller Part # 950

Pagina 4

9MODEL HS-5 POWER VENTER OUTPUT WIRING TO MAC-3(POWER VENTER MOTOR GREATER THAN 9 AMPS) MAC-3 PART # 950-0460 OUTPUT WIRING WITH A POWER VENTERWhen

Pagina 5

SEQUENCE OF OPERATION FOR POWER VENTER ON A SINGLE APPLIANCEThe following sequence of operation gives guidance as to how the Power Venter should opera

Pagina 6

LIMITED PARTS WARRANTY AND CLAIM PROCEDURETjernlund Products, Inc. warrants the components of its products for one year from date of installation. Th

Pagina 7 - HS-3 HS-4, HS-5

MAC-4 CONTROL WIRED WITH UP TO FOUR 24V GAS APPLIANCES AND MULTIPLE POWER VENTERS & IN-FORCERS (IF INDIVIDUAL OR COMBINED MOTOR LOAD EXCEEDS 1 H.P

Pagina 8

Copyright © 1997, Tjernlund Products, Inc. All rights reserved. P/N 8504031REV. A 9/99OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an

Pagina 9

TABLE OF CONTENTSPAGE(S)HS-3,4,5 DESCRIPTION ...

Pagina 10 - WARNING:

MODELSELECTIONTABLEINSTALLATION RESTRICTIONSFailure to install, maintain and/or operate the Power Venter in accordance with manufacturer's instru

Pagina 11

5. The Power Venter shall not be installed where the flue gas temperature exceeds 600oF. at the Power Venter inlet. Flue gas temperature verification

Pagina 12 - TJERNLUND PART # 950-0483

POWER VENTER MOUNTINGThe installer must supply plumber’s strap or 1/4” threaded rod with nuts and washers for mounting. The Power Venter may be mount-

Pagina 13

5FAN PROVING SWITCH INSTALLATIONNOTE: It is important that the electrical box is mounted with theFan Proving Switch in a vertical position.1. Mount su

Pagina 14

6MODEL HS-3, HS-4, HS-5 WIRING WITH SINGLE APPLIANCEThe HS-3, HS-4, and HS-5 Power Venters are equipped with 2 relays. One is used to activate the Pow